Smart Energy-Meter Reading & Theft-Anomaly Logger (SEM-TAL) is a buildable metering unit for a hostel block, a department building or a row of rented shops — the places where an institution's electricity bill usually goes wrong. A clamp-on current transformer (SCT-013-000) and a ZMPT101B voltage-sensing module feed an ESP32, which computes RMS voltage, RMS current, real power and running kWh every second, shows them on a 16x2 I2C LCD, and writes a 1-minute interval record to a microSD card. Over Wi-Fi, the node pushes the same records to a small Python (Flask + SQLite) dashboard that plots the daily load curve and lists every anomaly the firmware raised.
Three anomaly rules run on the device itself: (1) overload — current above the sanctioned limit for more than a few minutes; (2) tamper / direct hooking — load current detected while the voltage channel says the supply at the meter is effectively disconnected, the classic signature of a bypass; (3) off-hours surge — a night-time load profile far outside the learned baseline. Every flag carries an NTP-synced timestamp.
C firmware runs on the ESP32 (Arduino framework), which the VTU 2022 scheme teaches in the IoT lab; Python and Scilab/MATLAB handle the dashboard, calibration regression and load-profile analysis. Flask and SQLite are industry-standard extras beyond the syllabus, chosen because they keep the server small enough to explain end-to-end in the viva.
Hostels, department buildings and rented shops are billed from a single monthly meter reading, with no record of when energy was actually used. As a result, overloads from geysers and heaters go unnoticed until the breaker trips, suspected power theft or meter bypass cannot be evidenced or ruled out because there is no timestamped data, and disputes between owners and tenants degenerate into arguments. Commercial smart meters and DISCOM interval data are not accessible to a college or a small landlord.
There is a need for a low-cost, safe, buildable energy-monitoring node that measures single-phase consumption at 1-minute resolution, stores it locally so no data is lost, flags overload and tamper signatures as they happen, and presents the load profile and anomaly history on a simple dashboard — giving the warden or owner the same kind of evidence a DISCOM interval meter would, at a student-project price.
Synopsis
Abstract
Institutional and rental consumers in India rarely see their own consumption until the monthly bill arrives. This project builds a single-phase metering node that measures voltage, current, real power and energy, stores 1-minute interval records with timestamps, and raises on-device anomaly flags for overload, tamper and off-hours surges. A Flask + SQLite dashboard visualises the load curve and anomaly history. The unit was calibrated against a commercial clamp meter and a plug-in kWh meter and trialled for two weeks on a college building feeder.
Introduction
Hostels and small commercial rows are billed on one static meter that someone reads once a month. Between readings, nobody knows whether tonight's load was 2 kW or 8 kW, why the bill jumped last March, or whether a tenant has hooked a line directly off the pole. Interval metering answers all three — which is why distribution companies are moving to smart meters — but a commercial three-phase smart meter is out of a student's budget, and a hostel warden cannot request DISCOM interval data. A ₹2,300 open-hardware node fills the gap for study and demonstration.
Existing System
One electromechanical or basic static meter per building, read manually once a month; no interval data.
Theft and tampering surface only during a flying-squad inspection or after an abnormally high bill — weeks after the event.
Overloads (geysers, heaters, motors) trip the breaker repeatedly with no record of when.
Limitations: no timestamps, no load profile, no evidence trail, no early warning; disputes between tenants and owners are settled by argument, not data.
Proposed System
Sensing: non-invasive SCT-013-000 clamp CT (20 A working range) plus ZMPT101B mains-voltage module, so the circuit never touches mains directly.
Computation: the ESP32 samples both channels, computes true RMS and real power (mean of the v·i product, so power factor is measured, not assumed), and accumulates kWh.
Anomaly engine on-device: sanctioned-limit overload, current-with-no-voltage (tamper/direct hooking) and off-hours baseline breach, each debounced to suppress false alarms.
Storage and connectivity: every 1-minute interval goes to microSD first (source of truth), then in batches over Wi-Fi to the dashboard; missed Wi-Fi periods are back-filled from the card.
Dashboard: Flask + SQLite plots voltage/power curves, marks anomalies on the timeline and exports CSV for the report.
Feasibility Study
Technical: every stage is individually testable with instruments the department owns (DMM, clamp meter, plug-in kWh meter). OpenEnergyMonitor documents the exact burden and bias design used. The firmware uses well-documented Arduino-core APIs only.
Economic: the bill of materials is about ₹2,300 per node, one-time, with no subscription; the dashboard runs on an existing laptop.
Operational: installation is a clamp-and-go job for a licensed electrician — no rewiring, no meter-seal disturbance. Wardens read a browser page; training takes minutes. The main risk (working near 230 V AC) is contained by design: the CT clamps outside the insulation and the low-voltage side is powered by an isolated phone charger.
Objectives
01Measure single-phase RMS voltage, RMS current, real power and cumulative kWh using an SCT-013-000 CT and ZMPT101B module, calibrated against a clamp meter to within ±5% of reading.
02Compute RMS and real power in ESP32 firmware by sampling both channels over a whole number of mains cycles, so power factor is measured rather than assumed.
03Log a timestamped 1-minute interval record (V, I, W, Wh delta, flags) to microSD, with NTP time sync and automatic back-fill after Wi-Fi outages.
04Implement three debounced on-device anomaly rules: sanctioned-limit overload, current-with-no-voltage (tamper/direct-hooking signature) and off-hours baseline breach.
05Push intervals in batches over Wi-Fi to a Flask + SQLite dashboard that plots the load curve, marks anomalies and exports CSV.
06Characterise measurement error with Scilab/MATLAB regression across resistive and inductive loads and report it as a calibration table.
07Demonstrate the unit on a real building feeder for two weeks under a licensed electrician's supervision and summarise findings.
Scope
In scope
Single-phase 230 V AC feeders up to 20 A load, one metering node plus one dashboard.
Non-invasive CT-clamp measurement; the prototype does not replace or open the utility meter.
On-device anomaly rules (overload, tamper signature, off-hours surge) and interval logging to microSD + dashboard.
Calibration against department instruments (DMM, clamp meter, plug-in kWh meter) with a published error table.
Out of scope (v1)
Three-phase feeders, CTs above 20 A, and revenue-grade accuracy classes (IS/IEC 62053-21 type testing is a specialist lab activity).
Billing, tariff computation and any integration with BESCOM or other discom systems — the prototype is evidence, not a billing device.
Prepaid/vending mode and automatic disconnection via contactor.
Battery powering of the node itself (it runs from an isolated 5 V phone charger).
Methodology
The project follows the V-model, because every design stage on the left arm has a matching verification stage on the right arm — the discipline a measuring instrument demands.
Phase
Weeks
Activities
Deliverable
Requirements & literature survey
1–2
Study 8–12 papers on smart metering and theft detection; interview the hostel electrician; freeze requirements
SRS + Phase-I report draft
System design
3–4
Burden and bias network calculations, block diagram, SD record format, dashboard wireframes
Two weeks on the hostel mess feeder with electrician supervision
Trial data + findings
Documentation & viva prep
14
Final report, PPT, demo rehearsal
Submission
Testing approach: unit testing with instrument comparisons at each measurement stage; integration tests for SD retry and batch upload; black-box rule tests where each anomaly is deliberately provoked (a heater above the limit, a load running while the voltage channel is unplugged) and the flag, timestamp and debounce behaviour are checked against a written test-case table (ID, input, expected, actual, result); and a two-week acceptance trial whose data feeds the load-profile analysis in Scilab.
SEM-TAL is a classic IoT edge node plus a thin server. The sensing front end converts the CT's secondary current to a measurable voltage with a burden resistor and biases it to mid-rail so the ADC sees the full AC waveform; the ZMPT101B module scales mains voltage down to a safe level for the second ADC channel. The ESP32 firmware samples both channels at roughly 2 kHz over a 100 ms window (an integer number of 50 Hz cycles), computes RMS current, RMS voltage and the mean of the instantaneous v·i product (real power), accumulates Wh, evaluates the three anomaly rules, and writes one record per minute.
Storage is deliberately layered: microSD is the source of truth, Wi-Fi upload is opportunistic, and the dashboard can import a CSV straight off the card, so a viva demo never depends on college Wi-Fi.
flowchart TD
MAINS["230 V AC single-phase feeder"] -->|SCT-013 clamp, non-invasive| CT["SCT-013-000 current transformer"]
CT --> COND["Burden + bias network (33 ohm burden, 2 x 470k bias)"]
COND --> ADC1["ESP32 ADC1 GPIO34"]
MAINS -->|ZMPT101B module| ADC2["ESP32 ADC1 GPIO35"]
MCU["ESP32: C firmware (sampling, RMS, kWh, anomaly rules)"]
ADC1 --> MCU
ADC2 --> MCU
MCU --> LCD["16x2 I2C LCD (V, I, W, kWh pages)"]
MCU --> SD["microSD: 1-min interval records (SPI)"]
MCU -->|Wi-Fi, HTTP POST batch| DASH["Flask + SQLite dashboard on laptop"]
DASH --> CSV["CSV export + anomaly timeline"]
MCU --> NTP["NTP time sync"]
The dashboard keeps three SQLite tables (devices, intervals, anomalies), renders the load curve with an open-source JS charting library, and exports the same CSV the report uses. Firmware and server communicate with a documented 12-field JSON batch format, so either side can be replaced independently — useful when the team splits work four ways.
Modules
5 modules
Module 01
Metering Front End (Member A)
Sizes the burden resistor for the 20 A range using the OpenEnergyMonitor formula, builds the mid-rail bias network and RC anti-alias filter on perfboard, wires the ZMPT101B, and owns the calibration rig: 100 W bulb, 1 kW kettle and a clamp meter as reference. Deliverables are the per-channel calibration constants and the final error table.
Module 02
Firmware — Measurement & Display (Member B)
Implements the sampling loop over whole mains cycles, RMS and real-power computation, energy accumulator and rollover handling, the four-page LCD UI (V/I, W, kWh, last anomaly) with a mode button, and a watchdog so the node recovers by itself after a brown-out.
Module 03
Firmware — Logging & Anomaly Engine (Member C)
Owns NTP synchronisation, the 1-minute SD record writer with card-failure retry, the three anomaly rules with debounce timers and hysteresis, the offline ring-buffer that replays missed intervals when Wi-Fi returns, and the JSON batch uploader.
Module 04
Dashboard & Load-Profile Analysis (Member D)
Builds the Flask routes and SQLite schema, the load-curve page with anomaly markers, CSV import/export, and the Scilab scripts that regress measured error against the clamp-meter reference and plot a week's load profile for the report.
Module 05
Enclosure, Installation & Field Trial (shared)
Designs the IP-65 enclosure and CT-clamp mounting, performs the installation with the hostel's licensed electrician under the safety checklist, runs the two-week trial, maintains the daily logbook, and writes the field-trial chapter of the report.
Slides
12 slides · titles free · bullets, notes and the .pptx unlock
Slide 1
Smart Energy-Meter Reading & Theft-Anomaly Logger
Slide 2
Motivation
Slide 3
Problem Statement
Slide 4
Existing vs Proposed System
Slide 5
Objectives
Slide 6
Sensing Principle
Slide 7
System Architecture
Slide 8
Anomaly Rules
Slide 9
Calibration & Testing
Slide 10
Field Trial Results
Slide 11
Individual Contributions
Slide 12
Conclusion & Future Scope
Bullets, speaker notes and the .pptx · ₹2,000
The titles above are the real outline. The rest is what you present from.
Read each answer, close it, and say it in your own words. Your viva will ask. Now you'll know.
01Concept
Why use a clamp-on current transformer instead of a series shunt resistor?
A shunt must carry the full load current, so it inserts a live connection, dissipates heat and offers no galvanic isolation. The SCT-013 is a clamp that snaps over the insulated live wire, scales 100 A down to 50 mA at its secondary, and keeps the whole measurement circuitry isolated from mains — which is what makes a student build safe.
02Concept
Why do you measure the voltage channel when a CT alone already gives you current?
With only the CT we could estimate apparent power assuming a fixed 230 V and a power factor of 1, which is wrong for inductive loads like motors and pumps where the PF can be 0.6–0.8. Measuring both channels lets us compute real power as the mean of the instantaneous v·i product, so the kWh we log matches what the utility meter actually charges for.
03Concept
What is RMS and why do you compute it over a whole number of mains cycles?
RMS is the root-mean-square value — the DC equivalent that produces the same heating effect, which is what instrument ratings and bills use. We sample for a 100 ms window, exactly five 50 Hz cycles, because a partial cycle biases the mean of the v·i product and the squared current, producing visible error at low loads. A whole-cycle window cancels that bias.
+13 more questions, with answers
Try the free ones out loud first. Your examiner will not accept “it's in the PPT”.
Prepaid-style display: map accumulated kWh to the local tariff and show rupees on the LCD, with a UPI-based top-up alert as an extension.
MQTT + an open-source IoT platform (e.g., ThingsBoard) instead of direct HTTP, for multi-building deployments.
Three-phase and CT-ratio scaling for a full building panel, with per-phase anomaly rules.
Better anomaly detection: replace fixed thresholds with rolling-baseline statistics (per-hour mean ± k·σ) and simple pattern classification trained on the team's own logged data.
LoRa backhaul for feeders outside Wi-Fi coverage.
DISCOM-style interval reports — 96-slot daily profiles — as a teaching artefact showing how utilities study loss pockets.